2011年9月19日 星期一

PLC | mask cable connection? One side, both sides of the ground

[http://vkinngworld.blogspot.com/]


Are usually popular only take one side,
Can not both sides to ground.



Reason? WHY?
Check a lot of pages are finding out why.



I summarized this principle should be!!


Ground controllersground with other big power line can not be connected in series,
To be connected with the star-ground,
Is the fear of series equipment to the back-ground line,
Is not a zero potential.



So ☆ ground terminals each device will have different potential 


And becauseeach device ground terminals, have different potential


So: When the mask wire to ground connection on both sides, it will have a great current (magnetic field),
But affects the inside of the signal line.



V = the potential difference on both sides of the ground (assuming = 10V)
R = resistance of shielded cable (less than 10 ohms)

A = V / R = 10V/10 ohms = 1A

PLC|屏蔽線、隔離網接法?單邊、兩邊接地 PART-2

[http://vkinngworld.blogspot.com/]

上一篇當中,也許有人會覺得,
好像應該就是要單邊接地!!

其實不然,應該要看兩邊的設備是否有接地而定!!

如果是馬達跟控制器之間的配線,
隔離網就只要接單邊,
因為馬達跟控制器都有接地

但如果是控制器跟外部的sensor之間,
隔離網就要接雙邊,
因為sensor並沒有接地,控制器有接地。

所以屏蔽線、隔離網接單邊or兩邊接地,要看情形,
不是每種情形都合適。


用了耐撓曲線、高柔性電纜,還是一直斷線

[http://vkinngworld.blogspot.com/]

在戰車軌裡,已經用了耐撓曲線、高柔性電纜,怎麼還是一直斷線???

耐撓曲線、高柔性電纜,也是有等級區分的,
在型錄裡都會寫到,可以承受的最小曲度,
如果超過最小曲度,就不保證可使用壽命了。

當然越小的半徑,就是越貴的囉!!

以下圖為例:
在小於10米,最小變曲半徑=7.5 X d(電纜直徑)
在超過10米,最小變曲半徑=10 X d(電纜直徑)